Professional fire equipment providers
Your current location: Home > Product > Automatic Fire Alarm and Fire Linkage System > On site components
Product | PRODUCT
Functional Features:
The product is developed using a new methane sensor. Paired with it is the GK705Q combustible gas alarm control system, which achieves alarm monitoring function. Combustible gas detectors are used in residential areas and have a significant impact on households using methane gas. They can promptly activate the gas solenoid valve to cut off gas when the ambient gas concentration exceeds the standard.
Technical Parameter:
Working voltage: DC 24V pulse voltage
Static current: ≤ 10mA (bus)
Alarm current: ≤ 20mA
Dimensions: 95mm × 95mm × 37mm (including base)
Alarm concentration: 8% LEL (set threshold)
Measurement range: 0~20% LEL
Applicable gas: Methane (CH4)
Service life of gas sensor: 6 years.
Control output: A set of unidirectional active DC12V pulse outputs
Shell protection level: IP30
Fire alarm light: red; Fault light: yellow; Lifetime light: yellow; Work light: green
Usage environment:
Environmental temperature: -10 ℃ to+50 ℃
Relative humidity: ≤ 93 ± 3% RH (40 ℃± 2 ℃)