GT-BLJC-2LROE Ⅱ 1W-YSB713 (lifting floor single-sided upwards)

 

Functional Features:


Meet the design and usage requirements of GB17945-2010 "Fire Emergency Lighting and Evacuation Indication System" and GB51309-2018 "Design Standard for Fire Emergency Lighting and Evacuation Indication System";
The outer shell of the lamp is assembled from high-quality metal, flame-retardant plastic, and flame-retardant materials;
Adopting high brightness LED light source, low power consumption, uniform light emission, with contiPattern panel: single-sided up
Panel Material: Stainless Steel
Working voltage: DC18V~DC36V
DC insurance: 0.2A 60V
Protection level: IP30
Emergency transition time:<5s
Light source type: LED
Surface brightness: 50-300 (cd/㎡)
Main power consumption: 1W
Light source specifications: DC3.0V-DC3.2V 0.06W
Emergency time: 90 minutes
Lamp size: 352mm × 138mm × 7mmnuous, strobe, directional and other working modes, and with functions such as inspection, turning on and off lights;
Comes with PSN address code, non-polar two-wire wiring, simple wiring.

Technical Parameter:


Pattern panel: single-sided up
Panel Material: Stainless SteelOperating temperature: 0 ℃~55 ℃
Installation method: lifting

Working voltage: DC18V~DC36V
DC insurance: 0.2A 60V
Protection level: IP30
Emergency transition time:<5s
Light source type: LED
Surface brightness: 50-300 (cd/㎡)
Main power consumption: 1W
Light source specifications: DC3.0V-DC3.2V 0.06W
Emergency time: 90 minutes
Lamp size: 352mm × 138mm × 7mm

Usage environment:


Operating temperature: 0 ℃~55 ℃
Installation method: lifting