GT-BLJC-2LROE Ⅱ 1W-YSB713 (lifting floor single-sided downward)

 

Functional Features:


Meet the design and usage requirements of GB17945-2010 "Fire Emergency Lighting and Evacuation Indication System" and GB51309-2018 "Design Standard for Fire Emergency Lighting and Evacuation Indication System";
The outer shell of the lamp is assembled from high-quality metal, flame-retardant plastic, and flame-retardant materials;
Adopting high brightness LED light source, low power consumption, uniform light emission, with continuous, strobe, directional and other working modes, and with functions such as inspection, turning on and off lights;
Comes with PSN address code, non-polar two-wire wiring, simple wiring.

Technical Parameter:


Pattern panel: single-sided downward facing
Panel Material: Stainless Steel
Working voltage: DC18V~DC36V
DC insurance: 0.2A 60V
Protection level: IP30
Emergency transition time:<5s
Light source type: LED
Surface brightness: 50-300 (cd/㎡)
Main power consumption: 1W
Light source specifications: DC3.0V-DC3.2V 0.06W
Emergency time: 90 minutes
Lamp size: 352mm × 138mm × 7mm

Usage environment:


Operating temperature: 0 ℃~55 ℃
Installation method: lifting