S2003 Intrinsically Safe Zener Barrier EX

安全齐那珊S2003-up.jpg

Functional Features:


Connected to the GM748A circuit repeater, used for pairing with G7 encoded intrinsically safe explosion-proof equipment; Safety barriers need to be installed in safe areas.

Technical Parameter:


Intrinsic safety parameters: (3-4) Um: 125VAC/DC, Uo: 28VDC, 1o: 93mA, Po: 0.65W, Co: 0.05 μ F, Lo: 2.4mH
Um:125VACIDC、Uo:28VDC、lo:200mA、Po:1.4W、Co:0.42uF、Lo:2.8mH

Usage environment:


Environmental temperature; -20℃~+40℃
Relative humidity:<95% RH